Code Question of the Week Q: Table 508.3.3 of the 2006 International Building Code states that the separation between a Group B and a Group S-1 occupancy is permitted to be 0. Is it, therefore, the intent of this table to exempt the area calculation, as prescribed in Section 508.3.3.2, when utilizing the separated mixed-use design option? A: The answer is No. The sum of the ratios, as prescribed in Section 508.3.3.2, of the occupancy groups involved must still be equal to or less than 1.
Code opinions are the opinion of the staff but do not represent the official position of the International Code Council nor do they represent the views of any enforcing agency. The final interpretation of the code is the legal responsibility of the code official.
|
|